Quick Start
1. Place the programming link in position.
2. Connect DigiNet to the network with an Ethernet cable.
3. Connect a 12 volt DC power supply to the power terminals.
4. The LED's should now be illuminated. The amber LED may flicker occasionally.
5. Install and run the DigiNet Interface Software.
6. On the General page - select the PC comms port you will be using.
7. Connect a null modem lead between the PC com port and the DigiNet serial port.
8. Press the "Read From DigiNet" button.
9. You can now review the settings.
10. The next step will depend on your network settings. If you have a DHCP server (typically an ADSL router) proceed from section "With DHCP Server" otherwise go the section "Without DHCP Server".
With a DHCP Server
11. Ensure that the "Get Address Automatically" box is checked on the server page of the DigiNet Interface software. If it is not checked, then check it and download to DigiNet using the "Write To DigiNet" button on the general page.
12. Remove the programming link. The red LED should now flicker once or twice.
13. Wait for about 5 seconds and replace the programming link.
14. Read the data back from DigiNet as before.
15. The assigned IP address will now be displayed on the Server page. If this reads 0.0.0.0 then the DHCP process has failed and it will be necessary to set up the IP address manually. Follow the "Without DHCP Server" section instructions.
16. Make a note of the IP address and go to step 22.
Without a DHCP Server
17. You will need to set up the IP addressing manually. Uncheck the "Get Address Automatically" box on the server page of the DigiNet Interface software.
18. If there are a large number of devices on your network you will need to be assigned an IP address from your network administrator. If there are only a few PCs you can determine their address from a command prompt. Type in "ipconfig" and the settings will be returned. Make a note of each one and choose an address close to the ones returned changing only the fourth number. For example if your network is using 192.168.0.2 and 192.168.0.5 try using 192.168.0.6.
19. Enter the obtained number into the IP address boxes. You should be safe using 192.168.0.1 for the gateway address and 255.255.255.0 for the Submask.
20. Download the new data to DigiNet using the "Write To DigiNet" button on the general page.
When the download is complete - remove the programming link.
You should now be able to connect to DigiNet with a web browser. Enter the IP address in the
address field of the browser and the Status and Control page should appear. The page displays
the current status of the 16 digital and 4 analogue inputs of your DigiNet. You can control the
16 digital outputs by clicking on the Toggle buttons for the relevant output number.